Viewed products
Broad High Frequency Response: 5 MHz...
Used
Typically In Stock
Warning: Last items in stock!
Availability date:
Frequency Range | 5 MHz - 1 GHz |
Current Rating | 30 Amps max |
Application/Test Type | high frequency bulk injection testing. (works as sensitive monitoring probe) |
Insertion Loss | 6 to 30 dB |
Input | 50 watts max power |
Connector | N-Type, Female |
Aperture | 1.25" (32 mm) |
Weight | 4.2 lb.'s (1.9 kg) |
The AH Systems ICP-623 high frequency injection current probe is a device used with EMI measuring instruments to induce RF currents in accordance with MIL-STD 461 susceptibility testing. The conductor or cable under test is passed through the probe aperature and becomes a one-turn secondary winding (when injecting), or a one-turn primary (when receiving). This probe provides minimum insertion loss over its frequency of 5 MHz - 1 GHz.
See the CPF-631 Current Probe Calibration Fixture.
Typical specifications requiring the use of current injection probes are: