Impedance Stabilization Networks (Power and Data Lines)

Quick Links

Information

Viewed products

PMM L3-64/690V 690 Volt LISN for IEC 60309, UL1682, UL1686 - The EMC Shop View larger

PMM L3-64/690V 690 Volt LISN for IEC 60309, UL1682, UL1686

New

  • 9 kHz a 30 MHz frequency range
  • 63 A max output current
  • Large baseplate for optimal grounding
  • Local and remote control for PMM EMI receivers
  • Meets the requirements of several standards including IEC 60309, UL1682, UL1686

More details

Typically Stocked

Request Quote/More Info

Specifications

Voltage Rating400 VAC, 565 VDC (L-PE, N-PE) 690 VAC, 975 VDC (L-L, L-N)
Frequency Range9 kHz to 30 MHz
Standards MetIEC 60309; UL1682; UL1686; CISPR 16-1-2; VDE 0876; FCC part 15; MIL-STD 461F
RF ConnectorBNC (f)
Inductors50 Ω // [5 Ω + 50 µH] with 250 µH choke
Mains & EUT Connections4P5W connector
Current Rating63 Amps Max (IEC60309); 60 Amps Max (UL1682, UL1686)
Application/Test TypeAncillary device intended for repeatable and accurate measurement of the disturbance voltage that an EUT (Equipment Under Test) may inject into the power line or mains.
Dimensions465 x 450 x 740 mm (18 x 17.7 x 29 inches)
Weight50 kg (110 pounds)

Test Equipment Description

PMM L3-64/690V Description:

This PMM L3-64/690V model is made with CSA-listed connectors (Canada) (4P5W connector) and has a higher Maximum operating voltage (690 Vac; 975 Vdc) for IEC60309, UL1682, and UL1686.

The AMN - Artificial Mains Network, also known as LISN - Line Impedance Stabilization Network - is the ancillary device intended for repeatable and accurate measurement of the disturbance voltage that an EUT (Equipment Under Test) may inject into the power line or mains. This is obtained by providing well known impedance value and phase response across the frequency range of the test.

PMM L3-64 3-Phase, 64 Amp LISN for FCC Part 15 is suitable for measurement on AC 3-phase power circuits from DC to 60 Hz. The equivalent V-Network circuit of 50 Ω // (5 Ω + 50 μH) with 250 μH choke is fully compliant with the reference standards.

PMM Artificial Mains Networks provide robust and stable mechanical construction, high quality electric components, easy and perfect grounding, solid input-output power connections. They can be used in conjunction with any EMI receiver or spectrum analyzer and offer features required for safe, repeatable and accurate measurements.

PMM L3-64 Features:

  • 9 kHz a 30 MHz frequency range
  • 63 A max output current
  • Large baseplate for optimal grounding
  • Local and remote control for PMM EMI receivers
  • Meets the requirements of several standards including IEC 60309, UL1682, UL1686

Associated EMC Test Equipment