Availability date:
Standards Met | FCC 97-270 (part 68); IEC 60255-22-5; IEC 61000-4-11; IEC 61000-4-29; IEC 61000-4-4; IEC 61000-4-5; IEC 61000-4-8; IEC 61000-4-9; IEC 61326; IEC 61850-3 |
Application/Test Type | CE Marking - Cover transient and power fail requirements according to international standards for immunity tests |
Pulse voltage (open circuit) | 160V - 5,000V ± 10% |
Impedance | 2 Ohm |
Combination wave pulse 1, 2/50 - 8/20 μs (Hybrid-Surge pulse) Pulse conforms to IEC/EN 61000-4-5 | |
Parameter | Value |
Pulse current (short circuit) | Max. 2,500A ± 10% |
Coupling | Line to line;Line(s) to ground |
Repetition time | 10ms - 9,999ms |
Pulse repetition | max. 1Hz (1s - 999s) |
Phase synchronization | 0° - 360°, resolution 1° (16 - 500Hz) |
Polarity | positive / negative / alternating |
Coupling | L, N, PE; all combinations |
Phase synchronization | 0° - 360°, resolution 1° |
Dips, Interrupts & Variations Conforms to IEC/EN 61000-4-11, IEC/EN 61000-4-29 | |
Parameter | Value |
Dips, Interrupts & Variations | As per IEC/EN 61000-4-11,IEC/EN 61000-4-29 andIEC/EN 61000-6-1, -6-2 |
Test duration | 1 - 30,000 or endless, selectable |
Uvar with step transformer | 300V AC + DC |
Test duration | 0:01min - 99:59min |
Peak inrush current capability | 500 Amps |
Burst (EFT) 5/50 ns Pulse conforms to IEC/EN 61000-4-4 | |
Parameter | Value |
Pulse amplitude | 200V - 5,500V ± 10%;100V - 2,750V ± 10% into 50ohm |
Burst frequency | 0.1 kHz - 1,000 kHz |
Polarity | positive / negative |
Uvar with optional variac | N/A |
Switching times | Under 5us into a 100ohm resistive load |
Event time | 20us - 9,999s |
Repetition time | 10ms - 9,999s |
Phase synchronization | 0° - 360°, resolution 1° (16 - 500Hz) |
Burst time | 0.10ms - 999ms |
Dimensions | 19", 3HU |
Weight | 25 kg's (55 Lbs) |
The UCS 500N5 includes everything necessary to conduct fully compliant tests. The power mains supply for the controls and for the DUT is separate to render it more flexible to use with different DUT supply voltages.
The UCS 500N5 can be operated manually from the front panel or by remote via the built-in USB or GPIB interface. Fail inputs allow to control an ongoing test sequence based on the status of the DUT. Monitoring outputs (BNC) are offered for easy signal measurement and verification. Safety features such as interlock and warning lamp control are available.
Pre-programmed Standard Test routines allow highest user convenience. Still the UCS 500N5 offers the Quick Start test routine where parameters can be changed on-line during the test to evaluate the susceptibility level of an individual DUT.
The EM Test UCS 500N5 ultra-compact simulator is the most versatile tester to cover transient and power fail requirements according to international standards (basic and generic standards) and product/product family standards. The UCS 500N5 is the most economic solution for tests during development as well as for full-compliant immunity tests and CE Marking for single phase DUT with the ability to be extended for testing three-phase DUTs by means of an automatically controlled external coupling network up to 200A.
EM TEST supplies a large range of accessories for the various applications such as magnetic field tests.